8455新葡萄娱集团am

8455新葡萄娱集团am

8455新葡萄娱集团am
8455新葡萄娱集团am

产品类别

联系方式

电话:0755-26738591

传真:0755-26998440

网址:

邮箱:sales@octsources.com

地址:深圳市南山区虹步路39号大习科创大厦5F

产品类别 > 隔离器/转换器 > DCT-005A电流传感器

DCT-005A电流传感器

所属品牌:美国 OSI 来源:深圳市现代豪方仪器仪表点击:534次发布时间:2021-08-03

DCT-005A电流传感器


品牌:美国 OSI

 

型号:DCT

 

类型:DIN导轨式交流电流传感器

 

传感器输出由传感器的算术平均值导出,根据正弦波输入的RMS值进行输入和校准。

 


特点/FEATURES

•准确、可靠的测量.

15A范围都可用.

•紧凑的DIN导轨包装.

• Accurate, reliable measurement.

• Both 1 and 5A ranges are available.

• Compact DIN Rail packaging.






应用/APPLICATIONS

•设计用于需要性价比高的电流测量.

•设计用于需要CE和CSA的安装批准.

•非常适合需要DIN导轨安装的应用.

• Designed for use in OEM applications which require inexpensive current measurement.

• Designed for installations that require both CE and CSA approvals.

• Perfect for applications that require DIN-Rail mounting.






参数

电流输入

0-5Aac

输出

0-5Vdc、0-10Vdc、0-1mAdc、4-20mAdc、4-20mAdc回路

准确性

±0.5% FS

核心类型

直接的

频率

50-60Hz

测量

交流电

安装

DIN导轨

系统配置

 



型号选择

输入交

流电流

DCT型标准输出

0-1mVdc*

4-20mA

4-20mA**

0-10Vdc

0-5Vdc

0-1

001A

001E

001E2

001C

001CX5

0-5

005A

005E

005E5

005C

005CX5

 

注:*模型由测量线自供电.

**4-20mA回路供电型号需要12-32Vdc.

标准E、C和CX5型号需要100-135Vac仪表.

对于可选的220Vac仪表电源-添加后缀x“-22”.









规格

输入/INPUT

电流范围/Current

0-1A or 0-5A

频率范围/Frequency Range  

50-60Hz

负重/Burden

<1.5VA F.S.

电流过载/Current Overload

电流过载/Continuous

输入120%F.S.

1s,瞬态/1s, Transient

额定值0.20 X F.S.

介电试验/DIELECTRIC TEST

输入/输出/仪表电源/外壳

 Input/Output/Inst. Pwr./Case

3700Vac

仪表输出电源/外壳

Instrument Power to Output/Case

3700Vac

输出功率/Output to Case

490Vac

仪表电源/INSTRUMENT POWER

“A”型号

“E”、“C”、“CX5”型号

100-135Vac,50/60Hz,3.0VA

“E2”型号

12-32Vdc,回路供电

“-22”选项

230Vac,50/60Hz,±15%

输出/OUTPUT

输出负载

A”型

0-1mA输出)

0-15KΩ

“C”、“CX5”型(5V和10V)

最小2.5KΩ

“E”型

(4-20mA)

0-750Ω

“E2”型号

(回路供电)

0-600Ω@24V

响应时间

350ms

精确/ACCURACY

精确/ACCURACY

±0.5%F.S.@60Hz包括线性和设定点的影响

输出纹波/Output Ripple

低于1.0%P.P.

温度和物理/TEMPERATURE & PHYSICAL

工作范围/Operating Range

-10℃ to +55℃

终端Termination

电线尺寸高达10AWG

净重/Net Weight

0.65 lb








尺寸和连接/DIMENSIONS and CONNECTIONS 

















安装/操作/保修/INSTALLATION / OPERATION / WARRANTY

 

安装说明/INSTALLATION INSTRUCTIONS

1.只能由合格的电工进行安装!

2.在进行任何电气连接之前,确保电气服务已断开。

3.支路保护按国家和地方规范要求设置检查机构的报告。

4.按要求布线,并按照本表和装置上的接线图固定到端子上。

5.传感器适合安装在600Vac线路上。

6.为防止与带电电路接触,当安装在裸母线上时,要求传感器安装在需要使用工具进入的外壳中。当安装在绝缘电缆上时不需要第二个外壳的电缆。

1. Installation should be performed by qualifi ed electricians only!

2. Make sure electrical service is disconnected before making any electrical connections.

3. Branch circuit protection is required to be provided in accordance with the National and Local codes of the inspection authority.

4. Route wires as required and secure to terminals per connection diagram on this sheet and on the unit.

5. Transducers are suitable for installation on 600Vac lines.

6. To prevent contact with live circuits, when installed on a bare bus bar, the transducer is required to be mounted in an enclosure that requires the use of a tool for access. When installed on an insulated cable this second enclosure is not required.

 

 

操作说明/OPERATING INSTRUCTIONS

1.本装置适用于海拔2000米以下的室内使用。

2.根据安装类别(过电压)II,污染等级2的瞬态过电压。

3.如果需要清洁外表面,则应断电所有供应服务(两个测量和仪表电源电路),并用软刷刷洗或用低压空气吹扫。使用适当的眼部保护。不适合清洗软管。

4.最高相对湿度80%,温度最高31ºC,线性下降至50% 40℃时的相对湿度。

5.最大工作温度范围为-20°C至60°C。

1. This unit is intended for indoor use at altitudes up to 2000 meters.

2. Transient overvoltages according to Installation Category (overvoltage) II, Pollution Degree 2.

3. If cleaning of the exterior surface is necessary, de-energize all services of supply (both measuring and instrument power circuits) and brush with a soft brush or blow off with low-pressure air. Use appropriate eye protection. Not suitable for hose-down cleaning.

4. Maximum relative humidity 80 percent for temperatures up to 31ºC decreasing linearly to 50 percent relative humidity at 40ºC.

5. Maximum operating temperature range is -20°C to 60°C.




浏览了该产品的用户还浏览:

3ACT-001A电流传感器

3ACT-005A换能器

3ACT-010A传感器

3ACT-020A电流传感器

3ACT-025A换能器

8455新葡萄娱集团am客服
客服头部
8455新葡萄娱集团am
8455新葡萄娱集团am

扫一扫添加微信号